gForce GTR-410ASingle CircuitAir Cooled, Water/Glycol Cooled7 to 46 kW
10Energy Saver Coil - The Data Aire Energy Saver Coil is built into the system to provide total required capacity. Whenever the incoming water/glycol
11OPTIONS, continuedthe evaporator under full load will maintain pressure on the leaving side of the hot gas bypass valve to keep the valve port close
12MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046 CAPACITY in kW/hr - gross80° DB/67° WB Total 26,700 3
13MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046 FILTER SECTION Quantity 2 2 2 2 - - -Size - inches Dow
14MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046 ELECTRICAL SECTION Next Size FanElectrical data based
15MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046 CAPACITY in Btu/hr - gross80° DB/67° WB Total 27,900 41,30
16MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046 FILTER SECTION Quantity 2 2 2 2 - - -Size - inches
17AIR COOLED: Performance data at OPTIONAL airfl ow with remote air cooled condenser MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U
18AIR COOLED: Performance data at STANDARD airfl ow with remote outdoor condensing unitMODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD
19MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046 FILTER SECTION Quantity Size - inches Downfl ow 1-16x20x4 1
20AIR COOLED: Performance data at STANDARD airfl ow with remote outdoor condensing unitR-410AgForce GT also available in R-407C. Data in a separate b
21AIR COOLED: Performance data at STANDARD airfl ow with remote outdoor condensing unitMODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD
22AIR COOLED: Performance data at OPTIONAL airfl ow with remote outdoor condensing unitMODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD
23MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046 FILTER SECTION Quantity Size - inches Downfl ow 1-16x20x
24AIR COOLED: Performance Data at OPTIONAL airfl ow with remote outdoor condensing unitR-410AgForce GT also available in R-407C. Data in a separate b
25AIR COOLED: Performance data at OPTIONAL airfl ow with remote outdoor condensing unitMODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD
26MODEL NUMBER GTWD/U007 GTWD/U011 GTWD/U014 GTWD/U018 GTWD/U028 GTWD/U035 GTWD/U046 CAPACITY in Btu/hr - gross80° DB/67° WB Total 30,000 44
27MODEL NUMBER GTWD/U007 GTWD/U011 GTWD/U014 GTWD/U018 GTWD/U028 GTWD/U035 GTWD/U046FILTER SECTION Quantity 2 2 2 2 - - -Size - inches
28WATER COOLED: Performance data at STANDARD airfl owR-410AgForce GT also available in R-407C. Data in a separate brochure.MODEL NUMBER GTWD/U0
29WATER COOLED: Performance data at STANDARD airfl owMODEL NUMBER GTWD/U007 GTWD/U011 GTWD/U014 GTWD/U018 GTWD/U028 GTWD/U035 GTWD/U046 CONDENS
3… the pioneer and builder of the most complete line of precision cooling equipmentBack in the late 1960’s and early 70’s with the advancement of the
30WATER COOLED: Performance data at OPTIONAL airfl owMODEL NUMBER GTWD/U007 GTWD/U011 GTWD/U014 GTWD/U018 GTWD/U028 GTWD/U035 GTWD/U046 CAPACI
31WATER COOLED: Performance data at OPTIONAL airfl owR-410AgForce GT also available in R-407C. Data in a separate brochure.MODEL NUMBER GTWD/U0
32WATER COOLED: Performance data at OPTIONAL airfl owMODEL NUMBER GTWD/U007 GTWD/U011 GTWD/U014 GTWD/U018 GTWD/U028 GTWD/U035 GTWD/U046 ELECTRI
33WATER COOLED: Performance data at OPTIONAL airfl owMODEL NUMBER GTWD/U007 GTWD/U011 GTWD/U014 GTWD/U018 GTWD/U028 GTWD/U035 GTWD/U046 CONDEN
34GLYCOL COOLED: Performance data at STANDARD airfl owMODEL NUMBER GTGD/U007 GTGD/U011 GTGD/U014 GTGD/U018 GTGD/U028 GTGD/U035 GTGD/U046 CAPAC
35GLYCOL COOLED: Performance data at STANDARD airfl owR-410AgForce GT also available in R-407C. Data in a separate brochure.MODEL NUMBER GTGD/U0
36GLYCOL COOLED: Performance data at STANDARD airfl owMODEL NUMBER GTGD/U007 GTGD/U011 GTGD/U014 GTGD/U018 GTGD/U028 GTGD/U035 GTGD/U046 ELECT
37GLYCOL COOLED: Performance data at STANDARD airfl owMODEL NUMBER GTGD/U007 GTGD/U011 GTGD/U014 GTGD/U018 GTGD/U028 GTGD/U035 GTGD/U046 FLUID
38GLYCOL COOLED: Performance data at OPTIONAL airfl owMODEL NUMBER GTGD/U007 GTGD/U011 GTGD/U014 GTGD/U018 GTGD/U028 GTGD/U035 GTGD/U046 CAPACI
39GLYCOL COOLED: Performance data at OPTIONAL airfl owMODEL NUMBER GTGD/U007 GTGD/U011 GTGD/U014 GTGD/U018 GTGD/U028 GTGD/U035 GTGD/U046FILTER S
4Table of ContentsDesign features ... 7Control sy
40GLYCOL COOLED: Performance data at OPTIONAL airfl owMODEL NUMBER GTGD/U007 GTGD/U011 GTGD/U014 GTGD/U018 GTGD/U028 GTGD/U035 GTGD/U046ELECTRIC
41GLYCOL COOLED: Performance data at OPTIONAL airfl owMODEL NUMBER GTGD/U007 GTGD/U011 GTGD/U014 GTGD/U018 GTGD/U028 GTGD/U035 GTGD/U046 FLUID
42AUXILIARY CHILLED WATER: Performance data at STANDARD airfl owR-410AgForce GT also available in R-407C. Data in a separate brochure.Based on 45° F
43AUXILIARY CHILLED WATER: Performance data at OPTIONAL airfl owBased on 45° F entering fl uid temperature - 0% glycol.MODEL NUMBER GT*D/U007 GT*D
44ENERGY SAVER: Performance data at STANDARD airfl owR-410AgForce GT also available in R-407C. Data in a separate brochure.Based on 45° F entering fl
45ENERGY SAVER: Performance data at OPTIONAL airfl owR-410AgForce GT also available in R-407C. Data in a separate brochure.Based on 45° F entering fl
46gForce GT DX Downfl ow 7, 11, 14 and 18 kW
47gForce GT DX Upfl ow 7, 11, 14 and 18 kW
48gForce GT DX Downfl ow 28, 35 and 46 kW using Condensing units
49gForce GT DX Upfl ow 28, 35 and 46 kW using Condensing units
5IMPROVED PERFORMANCE andREDUCED MAINTENANCEBackward curved fans discharge air radially allowing for uniform static pressure across the raised fl oor.
50DATA TEMP Air Cooled Condensers, DARC 03 and 05, single circuit
51DATA TEMP Air Cooled Condensers, DARC 06-21, single circuit
52DATA TEMP Air Cooled Condensers, DARC 06-21, single circuit
53DATA TEMP Fluid Coolers, DAFC 06-30
54DATA TEMP Fluid Coolers, DAFC 06-30
55Standard Condenser Electrical Data 208/1/60 208/3/60 460/3/60 Model FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOPDARC 03 4.6/5.8/15 4.6/5.8/15 2.3/2.9/1
56 GUIDE SPECIFICATIONS 7-46 kW DX unitsComputer Room Air Conditioning Units(Floor Mounted, Direct Expansion, 7 to 46 kW)1.01 GENERALA. The
57 GUIDE SPECIFICATIONS 7-46 kW DX unitscoil shall be in a cross circuited or interlaced “A” frame arrangement to allow maximum coil surface
58 GUIDE SPECIFICATIONS 7-46 kW DX unitstype with complete overload protection on all three power lines, internal thermostats for winding pr
59 GUIDE SPECIFICATIONS 7-46 kW DX units1.08 WATER SENSORUnits shall be provided with one (1) water sensor. The solid state water sensor sha
6INCREASED THERMODYNAMICEFFICIENTIESgForce’s design incorporates rifl ed tubing cool-ing coils. Rifl e tubing is similar to borings in a gun barrel wh
60 GUIDE SPECIFICATIONS 7-46 kW DX unitsE. The following alarm functions shall be monitored and displayed when they occur in addition to enu
61 GUIDE SPECIFICATIONS 7-46 kW DX unitsThe following protocols shall be supported:Modbus RTU, TCP/IP or ASCHII SNMP V1 or V2BACnet IP or M
62 GUIDE SPECIFICATIONS 7-46 kW DX unitsfor fi eld installation and shall include sump, motor, and automatic control. The pumps shall be rate
63 GUIDE SPECIFICATIONS 7-46 kW DX units • Master unit fail safe mode allows slave units to revert their self control modeT. No Water Flow
gForceGT410-3/10
7FRAME AND CABINETThe heliarc welded tubular steel frame provides for maximum strength and ease of access. Side and front panels can be eas-ily opene
8DATA ALARM PROCESSOR-IIIThe Data Alarm Processor-III (DAP™ III) offers the defi nitive answer for precision environmental control. The DAP-III control
9PROTECTIVE and SAFETY FEATURESMetal shell enclosure with sealed front control panel Watch dog timerOpto-coupler signal inputs Protected 24VAC power